Wednesday, October 1, 2014

Limit Switch

90% Limit Switch Tripping

Model and serial number of the furnace

Model number __________________________________

          Serial number __________________________________

          Control Board Part Number ________________________

          Model Plug Part Number __________________________

          Note: If the control was replaced from another unit, the model
          plug may be the wrong part number for this model furnace.

          58 Series furnaces: Refer to unit wiring diagram
          59 Series furnaces: Refer to unit rating plate

Model and serial number of the "N" coil

Model number __________________________________

          Serial number __________________________________


Model and serial number of the outdoor unit

          Model number __________________________________

          Serial number __________________________________

Does the limit trip in (circle as many as applies)

Low heat                 Medium heat                     High heat

What is the temperature rise in:

Low heat                 Medium heat                     High heat

Is a by-pass humidifier installed?

Manifold pressure set with burner box cover off?
Remember: for natural gas on Step Modulating furnaces manifold pressure is set as follows: Medium heat, high heat then low heat.


Is this a propane installation?

For propane on Step Modulating furnaces manifold pressure is set as follows:  high heat, medium heat then low heat

For variable speed airflow selections, refer to the appropriate box below. Airflow selection methods for Infinity/Evolution systems are different than the method for variable speed furnaces controlled by a thermostat.

If the furnace is controlled by a User Interface, do a complete re-install or perform a duct assessment. Note what the duct system static pressure is. If the static pressure is over 1.00 esp, look for restrictions or obstructions in the duct system such as:

Dirty filter
High pressure drop filter
Dirty evaporator coil
Dirty condensing heat exchanger coil
Supply dampers closed
Zone dampers wired backward
Supply registers closed or blocked
Return grills blocked


Air Flow Adjustments:

Is this an Infinity/Evolution System?
Note: Do not make any changes at the furnace control board. All furnace options are configured at the User Interface.

Was the airflow setting on the U.I. changed from "Comfort" to "Efficiency"?
This will increase the airflow in certain modes, depending on the type of furnace. See Note: below.

Note: On 2 stage VSP models, when the Comfort/Efficiency setting is changed to “Efficiency”, All models (except the 40,000 BTUH model) the Low Heat airflow is increased by 7 percent and High Heat airflow is increased 8 percent for maximum comfort. On 40,000 BTUH models the Low Heat airflow will increase by 11 percent and High Heat airflow is increased 10 percent. Factory default setting is “Comfort” at the U.I. or “ON” at the furnace control.

Note: On Step Modulating models, when the Comfort/Efficiency setting is changed to “Efficiency”, Low Heat airflow is increased by 9 percent, Medium Heat airflow is increased by 7 percent and High Heat airflow is increased 15 percent for maximum efficiency. 

Is the Low Heat Rise or Low/Med Heat Rise setting on the U.I. turned “ON”?
This will increase the airflow in certain modes, depending on the type of furnace. See Note: below.

           Note: When the Low Heat Rise or Low/Med Heat Rise is turned “ON”, it increases Low Heat (2 stage VSP models) airflow or Low and Medium Heat (Step Mod models) airflow by 18 percent. This compensates for increased return air temperature from bypass humidifiers.

The maximum airflow increase when the U.I. is set for “Efficiencyand the Low Heat Rise (or Low/Medium Heat Rise) is turned “ON” is:

           For 2-stage models, 18% in Low Heat
                                             8% in High Heat (10% for 40,000 BTUH models)

           For Step-Modulating Models, 18% in Low Heat
                                                          18% in Medium Heat
                                                          15% in High Heat



Is this a variable speed furnace on a non-Infinity/Evolution System?

Is the Comfort/Efficiency, SW 1-4 switch turned “OFF” at the furnace control?
This will increase the airflow in certain modes, depending on the type of furnace. See Note: below.

          Note: On 2 stage VSP models, when SW 1-4 is turned “OFF”, Low Heat
          airflow is increased by 7 percent and High Heat airflow is increased 8
          percent for maximum comfort. On 040 units the Low Heat airflow will
          increase by 11 percent and High Heat airflow is increased 10 percent.   
          Factory default setting is “Comfort” at the U.I. or “ON” at the furnace  
          control.   
         
         Note: On Step Modulating models, when SW 1-4 is turned “OFF”, Low  
         Heat airflow is increased by 9 percent, Medium Heat airflow is increased by
         7 percent and High Heat airflow is increased 15 percent for maximum
         efficiency. 

Is the Low Heat Rise switch, SW 1-3 turned “ON” at the furnace control?
This will increase the airflow in certain modes, depending on the type of furnace. See Note: below.

          Note: When SW 1-3 is turned “ON”, it increases Low Heat (2 stage VSP
          models) airflow or Low and Medium Heat (Step Mod models) airflow by 18  
          percent. This compensates for increased return air temperature from  
          bypass humidifiers.

The maximum airflow increase when SW1-4 is turned “OFFand SW1-3 is turned “ON” is:

           For 2-stage models, 18% in Low Heat
                                             8% in High Heat (10% for 40,000 btuh models)

           For Step-Modulating Models, 18% in Low Heat
                                                          18% in Medium Heat
                                                          15% in High Heat




Increase the blower off delay time. The limit may be tripping after the call for heat has terminated.

Change all settings at the U.I. for Infinity/Evolution systems or at the furnace control for Non-Infinity/Evolution systems to see if the limit switch tripping issue is eliminated-Remember to save your changes when exiting the U.I!

For other non-variable speed 90% units with PSC blowers verify that the correct speed tap is selected.

For all units continue below:

Is it the correct limit and shield installed?
For Step Modulating Units, refer to the list of limits and shield at the end of this checklist. You can also refer to EPIC for the correct limit and shield combination for the model you furnace have.

 Is the limit shield touching the side of the primary heat exchanger?
Slightly re-bend the shield to make sure it does not touch the primary HX. Do not over-bend the shield
Make sure the tab that mounts the shield to the cell panel is not bent more than 90 degrees.




Note how one side of the limit shield is touching the primary heat exchanger. This will cause the limit switch to trip in Low Heat (58MVB/355AAV) and Medium Heat (58MVC/355CAV)


While the limit shield is removed from the cell panel; check to see if the Rear Air Baffle is installed across the top rear of the condensing heat exchanger. You may also be able view this baffle by through the open area of the N coil or removing the blower and looking up between the secondary heat exchanger cells.

The baffle is a 322052-301 through 309 for Step Modulating condensing furnaces. Refer to the table at the end of this checklist for the correct air baffle.  For other 90% models, refer to EPIC.

Return air connections

          Left side of furnace (motor side)        Right side of furnace    Bottom

          Combination:           Both sides     Right Side/Bottom   Left side/Bottom

Actual CFM in:         

Low heat_________          Medium heat_________                                 

High heat________           Cooling__________

Note: A duct traverse is required to get the actual CFM



Actual Esp in:

Low heat_________          Medium heat_________                                 

High heat________           Cooling__________
         
Actual Blower Motor RPM in:        

Low heat_________          Medium heat_________                                 

High heat________           Cooling__________

The Blower Motor RPM can be obtained from the User Interface

Is this a factory supplied cased or uncased coil?

Supply the dimensions of the coil or casing in the drawing at the end of this checklist.
  

N-Coil Installation:

Is this an uncased N coil?

          How high above the furnace is the coil installed?

          Is the opening in the mounting pan or shelf as large as the coil opening?

Is this a cased N coil?

Check the intake air box underneath the burner box. Does the intake air box have both combustion air disks installed? Most furnaces and venting sizes require both combustion air disks installed. The exception would be the 120 and 140 size furnaces using standard 3 inch elbows and high altitude installations.
Refer to the venting table including the notes at the bottom of the page.

Clean the trap and collector box assembly. Water build up can cause the pressure switch to trip, which will cause the inducer to ramp up to re-close the pressure switch. On modulating furnaces, this can energize the high stage of the gas valve and cause high gas flow while the furnace is in medium heat.

Step Modulating Limit, Shield and Rear Air Baffle Dimensions:

Model
Limit
Shield
Rear Air Baffle
Baffle Dimensions
58MVC060-14
HH12ZB200
320711-303
None
None
58MVC080-14
HH12ZB180
320711-302
322052-302
11.9” x 4”
58MVC080-20
HH12ZB180
320711-302
322052-302
11.9” x 4”
58MVC100-20
HH12ZB180
320711-302
322052-303
14.9” x 5”
58MVC120-20
HH12ZB170
320711-302
322052-309
14.9” x 5”

Model
Limit
Shield
Rear Air Baffle
Baffle Dimensions
355CAV042060
HH12ZB200
320711-303
None
None
355CAV042080
HH12ZB180
320711-302
322052-302
11.9” x 4”
355CAV060080
HH12ZB180
320711-302
322052-302
11.9” x 4”
355CAV060100
HH12ZB180
320711-302
322052-303
14.9” x 5”
355CAV060120
HH12ZB170
320711-302
322052-309
14.9” x 5”

Model
Limit
Shield
Rear Air Baffle
Baffle Dimensions
58MVB040-14
HH12ZB200
320711-302
None
None
58MVB060-14
HH12ZB200
320711-303
None
None
58MVB080-14
HH12ZB180
320711-302
322052-302
11.9” x 4”
58MVB080-20
HH12ZB180
320711-302
322052-302
11.9” x 4”
58MVB100-20
HH12ZB180
320711-302
322052-303
14.9” x 5”
58MVB120-20
HH12ZB170
320711-302
322052-309
14.9” x 5”

Model
Limit
Shield
Rear Air Baffle
Baffle Dimensions
355AAV042040
HH12ZB200
320711-302
None
None
355AAV042060
HH12ZB200
320711-303
None
None
355AAV042080
HH12ZB180
320711-302
322052-302
11.9” x 4”
355AAV060080
HH12ZB180
320711-302
322052-302
11.9” x 4”
355AAV060100
HH12ZB180
320711-302
322052-303
14.9” x 5”
355AAV060120
HH12ZB170
320711-302
322052-309
14.9” x 5”

320711-302
No Hole in Shield
320711-303
1” Hole in Shield


See location of Rear Air Baffle below and on next page:









Monday, September 1, 2014

ECM Motors

TECH TALK
I often get calls from technicians wondering what the “best” way is to test an ECM motor.  That’s a difficult question to answer in less than 30 seconds.  The Carrier/Bryant factory publishes a very comprehensive diagnostic troubleshooting guide, but rarely have I seen anyone actually use it.  That being said, I decided it would be best to publish a short article on quick ECM motor diagnostic techniques.

Before getting into the actual checks, let’s make sure we understand the basics of how ECM motors work.  The ECM blower motor is first fed 120 VAC power through the 5-pin connector.  The 120 VAC power is then rectified to DC by a diode module.  After rectification, the DC signal is electronically commutated and fed in sequential order to 3 stator windings. The frequency of commutation
pulses determines motor speed.  In a nutshell, the P.C. Board is communicating with the module to determine Torque, RPM and Pulse Frequency. 

Knowing this helps to understand that even with voltage present, the circuit board communications need to be active and functioning for the motor to work.  The motor module must also be functioning to properly control the motor.  If either is defective, the motor will not turn.

First.   Initiate a call for fan on the circuit board or from the thermostat and check with your meter for 120 VAC at the motor.  2.  If there is 120 VAC present then turn power off to the furnace or fan coil and remove the blower.  Then remove the motor module and visually inspect for damage or burnt components inside.  3.   Turn the motor and see if it turns freely.  Note that the motor has an internal brake and will stop the wheel before too many revolutions.  4.  Set your OHM meter to the highest setting and OHM each of the 3 motor leads to the un-painted motor end shield.  You should read > 100k OHMs on each lead.  If so, the motor passes this test.  5.  OHM out each of the 3 leads to each other (1 to 2, 1 to 3 & 2 to 3).  Each should read less than 20 OHMS and should be nearly equal or within + 10%.  6.  If the motor turns freely and passes the listed OHM’s tests, the motor is fine.  You either have a bad module or bad circuit board. 

Most of the time the motor is fine, but the module or circuit board has failed.  At this point, if you don’t have a definitive answer on which component is bad, you should refer to the manufacturer’s detailed troubleshooting guide or purchase a TECMate Pro tester.  This will simulate the circuit board’s call for fan by allowing you to manually turn the fan on/off.  If you are able to energize the fan with the TECMate Pro, then you have a bad circuit board or wiring harness.  The part number for the TECMate Pro is: GE-A447 and is available at our store.  The good news is that this TECMate Pro will work on all or most all Genteq ECM motors used in our industry.  The exception is the X-13 motor.  It is not designed to work on the X-13.  

The specific ECM troubleshooting guide for the Carrier/Bryant product you’re working on can be downloaded from www.HVACPartners.com.   You may also want to refer to www.dealertoolbox.com or download the Genteq App from the App store for additional troubleshooting references.

Although this is not a 100% comprehensive troubleshooting guide on ECM motors, many times this “short list” of troubleshooting tips will lead you to the problem and save you a significant amount of time

Good Luck


Magnum